Data Sheet
RS485 HUBs (H01 - H03)
H01 H02 H03 |
Features
|
Introduction
The products from the H01-H03 family are reliable RS485 signal hubs made to work with variable transmission speeds. They allow flexible branching of the 1:3 interface while simultaneously protecting the attached devices thanks to internal 3 kV/DC galvanic isolation. Additionally, dedicated EMC protections will improve transmission quality and limit the impact of interference typical for an industrial environment.
Specifications
Redisage PN |
H01 |
H02 |
H03 |
||||
Input | 1 x RS485 channel; Data+, Data- | ||||||
Output | 3 x RS485 channels; Data+, Data- | ||||||
Power |
Voltage |
12-30 VDC / 24 VAC |
12-30 VDC |
||||
Power | < 1 W | ||||||
Frame ground protection | yes | ||||||
3000 VDC isolation |
3-way |
branched side |
main side |
||||
Baud rate |
up to 115200 bps |
||||||
LED indicators | communication Tx, Rx and power | ||||||
RS485 termination | 120 ohm manually enabled | ||||||
Connector |
RS485 | 8-pin terminal block max. 2.5 mm2 wire | |||||
Power | 3-pin terminal block max. 2.5 mm2 wire | ||||||
Transmission |
RS485 |
max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps |
|||||
Mounting and enclosure | DIN rail, plastic PA - UL 94 V0, black/green | ||||||
Temperatures | -40°C to +75°C operating and storage |
||||||
Humidity | 10 - 90% RH, non-condensing | ||||||
ESD protection |
±4 kV contact discharge / ±8 kV air discharge |
||||||
Certification |
CE, |
||||||
Norms |
61000-6-2 - Immunity standard for industrial environments 61000-6-4 - Emission standard for industrial environments |
Variants
H01 - THREE-WAY Isolated RS485 HUB

H02 - Branched Side Isolated RS485 HUB

H03 - Main Side Isolated RS485 HUB

{{@169}}
Pin assignments
H01 |
H02 |
H03 |
{{@221#bkmrk-enclosure-dimensions}}
{{@221#bkmrk-1u-module-enclosure.}}
{{@221#bkmrk-}}
{{@168}}
SR-D