Data Sheet
H01 H02 H03 |
Features
|
Introduction
The products from the H01-H03 family are reliable RS485 signal hubs made to work with the variable transmission speeds. They allow flexible branching of 1:3 interface while simultaneously providing protection for the attached devices thanks to internal 3 kV/DC galvanic isolation. Additionally, dedicated EMC protections will improve transmission quality and limit the impact of interference typical for an industrial environment.
Specifications
Redisage PN |
H01 |
H02 |
H03 |
|
---|---|---|---|---|
Input | 1 x RS485 channel; Data+, Data- | |||
Output | 3 x RS485 channels; Data+, Data- | |||
Power |
Voltage |
12-30 VDC / 24 VAC |
12-30 VDC |
|
Power | < 1 W | |||
Frame ground protection | yes | |||
3000 VDC isolation |
3-way |
branched side |
main side |
|
Baud rate |
up to 115200 bps |
|||
LED indicators | communication Tx, Rx and power | |||
RS485 termination | 120 ohm manually enabled | |||
Connector |
RS485 | 8 pin terminal block max. 2.5 mm2 wire | ||
Power | 3 pin terminal block max. 2.5 mm2 wire | |||
Transmission |
RS485 |
max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps |
||
Mounting and enclosure | DIN rail, plastic PA - UL 94 V0, black/green | |||
Temperatures | -40°C to +75°C operating and storage |
|||
Humidity | 10 - 90% RH, non-condensing | |||
ESD protection |
±4 kV contact discharge / ±8 kV air discharge |
|||
Certification | CE, RoHS |
Variants
H01 - 3-way Isolated RS485 HUB
H02 - Branched Side Isolated RS485 HUB
H03 - Main Side Isolated RS485 HUB
Frame ground FG
Electronic circuits are constantly prone to electrostatic discharge ESD. Redisage Electronics modules feature a design for the frame ground terminal block FG. The frame ground provides a path for bypassing ESD, which provides enhanced static protection ESD abilities and ensures the module is more reliable. Connecting FG terminal block to the earth ground will bypass the ESD disturbances outside the device so will provide a better level of protection against ESD.
Frame Ground FG connection reference drawing is provided below.
If earth ground is not available FG can be left floating or it can be connected with the power supply GND.
Pin assignments
H01 |
H02 |
H03 |
Enclosure dimensions
1U Module Enclosure.
98 x 17.5 x 56.4