Data Sheet
R01 R02 R03 R04 |
Features
|
Introduction
The R01 provides 3-way optical isolation between both RS485 sides and power supply. It can also be used as a repeater to extend the transmission of an existing network. Additionally, an RS485 system can be expanded beyond the 256 nodes limitation imposed by the standard.
The R02 is exactly the same as the R01, except for the isolation range. The R02 has one RS485 side isolation.
The R03 separator module provides a complete full-duplex, 3-way electrical isolation channel between two RS232 devices. This isolation is an important consideration if a system uses different power sources, has noisy signals or must operate at different ground potentials.
The R04 is exactly the same as the R03, except for the isolation range. The R04 has one RS232 side isolation.
Specifications
Redisage PN |
R01 |
R02 |
R03 |
R04 |
|
---|---|---|---|---|---|
Repeater ports | 2 x RS485 | 2 x RS232 | |||
Power |
Voltage |
12-30 VDC / 24 VAC |
12-30 VDC |
12-30 VDC / 24 VAC |
12-30 VDC |
Power | < 1 W | ||||
Frame ground protection | yes | ||||
Serial |
RS232 | N/A | TxD, RxD, GND | ||
RS485 | A, B | N/A | |||
3000 VDC isolation |
3-way |
single side |
3-way |
single side |
|
Baud rate |
up to 115200 bps |
||||
LED indicators | communication Tx, Rx and power | ||||
RS485 Termination | 120 ohm manually enabled | N/A | |||
Connector | RS232 | N/A | 3 pin terminal block max. 2.5 mm2 wire | ||
RS485 | 3 pin terminal block max. 2.5 mm2 wire | N/A | |||
Power | 3 pin terminal block max. 2.5 mm2 wire | ||||
Transmission |
RS485 |
max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps |
|||
RS232 | max. 15 m at 115.2 kbps | ||||
Mounting and enclosure | DIN rail, plastic PA - UL 94 V0, black/green | ||||
Temperatures | -40°C to +75°C operating and storage |
||||
Humidity | 10 - 90% RH, non-condensing | ||||
ESD protection |
±4 kV contact discharge / ±8 kV air discharge |
||||
Certification | CE, RoHS |