Data Sheet
C10 C11 C12 C13 |
Features
|
Introduction
Most industrial computer systems provide standard RS232 serial ports. Though widely accepted, RS232 has limited transmission speed, range, and networking capabilities.
The RS485 standards overcome these limitations by using differential voltage lines for data and control signals, which transparently convert RS232 signals into isolated RS485 signal with no need to change any hardware or software.
The C10 lets you easily build an industrial grade, a long-distance communication system using standard PC hardware.
The design of the isolation between the C10 - C12 is different. If the user wants to supply power from the PLC/PC, the C10 or C12 should be used, otherwise, the isolation will be broken.
Specification
Redisage PN |
C10 | C11 | C12 | C13 | ||||||||
Converter ports |
1 x RS232 & 1 x RS485 |
|||||||||||
Power |
Voltage |
12-30 VDC / 24 VAC |
12-30 VDC |
|
||||||||
Power | < |
|||||||||||
Frame |
yes |
|||||||||||
Serial
|
RS232 | TxD, |
||||||||||
RS485 | A, B |
|||||||||||
3000 VDC |
3- |
on RS232 side |
on RS485 side |
|
||||||||
Baud rate |
up to 115200 bps |
|||||||||||
LED indicators |
communication Tx, | |||||||||||
RS485 termination |
120 ohm manually enabled | |||||||||||
Connector |
RS232 | 3 pin terminal block max. 2.5 mm2 wire | ||||||||||
RS485 | 3 pin terminal block max. 2.5 mm2 wire | |||||||||||
Power | 3 pin terminal block max. 2.5 mm2 wire | |||||||||||
Transmission
|
RS485 |
max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps |
||||||||||
RS232 | max. 15 m at 115.2 kbps |
|||||||||||
Mounting and enclosure | ||||||||||||
-40°C to +75°C operating and storage |
||||||||||||
Humidity | 10 - 90% RH, non-condensing |
|||||||||||
ESD protection |
±4 kV contact discharge / ±8 kV air discharge |
|||||||||||
Certification |
CE, RoHS |
Applications
C10 - 3-way isolated