Configuration by the Serial Console

Modbus TCP/RTU Gateways (G04)

Another way to configure the device is via a serial console. In case of the G11 - G13 Modbus gateways an additional USB/UART converter is needed.

Procedure to enter serial console mode
  • Turn off the power of the device.
  • Connect Ethernet converter to the dedicated USB/UART converter via the microUSB port.
  • Connect the USB/UART converter to the PC.
  • Open the serial console (default baud rate is 115200 bps).
  • Short the FG and GND ports.
  • Turn on the power.
  • Wait until the ST indicator (orange LED) lights up (it should light up after red light - service mode).
  • Open the the FG and GND ports.
  • Login using user’s personal credentials or default login details.
  • If the process is successful, configuration command can be typed into the terminal.

image.png

List of all commands