Configuration by the Serial Console
Modbus TCP/RTU Gateways (G04)
Another way to configure the device is via a serial console. In case of the G11 - G13 Modbus gateways an additional USB/UART converter is needed.
Procedure to enter serial console mode
- Turn off the power of the device.
- Connect Ethernet converter to the dedicated USB/UART converter via the microUSB port.
- Connect the USB/UART converter to the PC.
- Open the serial console (default baud rate is 115200 bps).
- Short the FG and GND ports.
- Turn on the power.
- Wait until the ST indicator (orange LED) lights up (it should light up after red light - service mode).
- Open the the FG and GND ports.
- Login using user’s personal credentials or default login details.
- If the process is successful, configuration command can be typed into the terminal.
List of all commands