Hardware
RemoteCOM can be installed on any device from the Redisage C20 - C25 Ethernet Converters family.
Features
Frame Ground FG
Electronic circuits are constantly prone to electrostatic discharge ESD.
Redisage Electronics modules feature a design for the frame ground terminal block FG.
The frame ground provides a path for bypassing ESD which provides enhanced static protection ESD abilities and ensures the module is more reliable.
Connecting FG terminal block to the earth ground will bypass the ESD disturbances outside the device so it will provide a better level of protection against ESD.
Frame Ground FG connection reference drawing is provided below.
If earth ground is not availabe FG can be left floating or it can be connected with power supply GND.
Specification
Redisage PN |
C20 |
C21 |
C22 |
C23 |
C24 |
C25 |
|
---|---|---|---|---|---|---|---|
Ports |
RS232 |
2x |
- |
- |
4x |
- |
2x |
RS485 |
- |
1x |
- |
- |
4x |
2x |
|
RS232/RS485 |
- |
- |
2x |
- |
- |
- |
|
Microcontroller |
ESP32 |
STM32F4 |
|||||
WiFi |
N/A |
||||||
Power |
Voltage |
12-30 VDC |
|||||
Power |
< 1W |
||||||
Frame ground connection |
yes |
||||||
Baud rate |
up to 115200 bps |
||||||
LED indicators |
communication Tx, Rx and power |
||||||
RS485 termination |
120 ohm manually enabled |
||||||
Connector |
RS232/RS485 |
8 pin terminal block max. 2.5 mm2 wire |
|||||
Power |
3 pin terminal block max. 2.5 mm2 wire |
||||||
Ethernet |
RJ45 |
||||||
Transmission |
RS485 |
max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps |
|||||
Mounting and enclosure |
DIN rail, plastic PA - UL 94 V0, black/green |
||||||
Temperatures |
-40°C to +75°C operating and storage |
||||||
Humidity |
10 - 90% RH, non-condensing |
||||||
ESD protection |
±4 kV contact discharge / ±8 kV air discharge |
||||||
Certification |
CE, RoHS |
LED indicatorsIndicators
Pin assignmentsAssignments
C20 |
C21 |
C22 |
C23 |
C24 |
C25 |
In the C22 converter user should use only RS232 or only RS485 interface of one port as they occupy the same internal bus of the device.