Hardware
RemoteCOM can be installed on any device from the Redisage C20 - C25 Ethernet Converters family.
Features
Features
|
|
Ethernet converter to RS232/RS485
|
ESD protection for the RS485 data line
|
Power supply: +12 to +30 VDC
|
Transmission speed up to 115200 bps
|
Tx, Rx and power LED indicators
|
RS485 embedded termination 120 ohm
|
Operating temperatures: -40°C to +75°C
|
DIN rail mounting
|
Dimensions: 90x56.4x22.5 mm
|
3 years warranty
|
Customization of OEM is welcomed
|
{{@169#bkmrk-frame-ground-fg}}
{{@169#bkmrk-electronic-circuits-}}
{{@169#bkmrk-frame-ground-fg-conn}}
{{@169#bkmrk-if-earth-ground-is-n}}
Specification
{{@170#bkmrk-specifications}}
Redisage PN{{@170#bkmrk-redisage-pn-c20-c21-}}
|
C20
|
C21
|
C22
|
C23
|
C24
|
C25
|
---|
Ports
|
RS232
|
2x
|
-
|
-
|
4x
|
-
|
2x
|
RS485
|
-
|
1x
|
-
|
-
|
4x
|
2x
|
RS232/RS485
|
-
|
-
|
2x
|
-
|
-
|
-
|
Microcontroller
|
ESP32
|
STM32F4
|
WiFi
|
N/A
|
Power
|
Voltage
|
12-30 VDC
|
Power
|
< 1 W
|
Frame ground connection
|
yes
|
Baud rate
|
up to 115200 bps
|
LED indicators
|
communication Tx, Rx and power
|
RS485 termination
|
120 ohm manually enabled
|
Connector
|
RS232/RS485
|
8 pin terminal block max. 2.5 mm2 wire
|
Power
|
3 pin terminal block max. 2.5 mm2 wire
|
Ethernet
|
RJ45
|
Transmission
distance
|
RS485
|
max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps
(Belden 9841 2P twisted-pair cable, if different cables are used,
the transmission distance may change)
|
RS232
|
max. 15 m at 115.2 kbps
|
Mounting and enclosure
|
DIN rail, plastic PA - UL 94 V0, black/green
|
Temperatures
|
-40°C to +75°C operating and storage
|
Humidity
|
10 - 90% RH, non-condensing
|
ESD protection
|
±4 kV contact discharge / ±8 kV air discharge
|
Certification
|
CE, RoHS
|
LED indicators
Converters C20 - C22
|
Converters C23 - C25
|
|
|
LED indicator
|
Color
|
Function
|
LED indicator
|
Color
|
Function
|
PW
|
Blue
|
Power
|
PW
|
Blue
|
Power
|
ETH
|
Green
|
Network activity
|
ETH
|
Green
|
Network activity
|
ST
|
Orange
|
Console mode
|
CN
|
Yellow
|
Console mode
|
Red
|
Service mode
|
COM
|
Green
|
RS232/RS485 activity
|
|
SR
|
Red
|
Service mode
|
ER
|
Yellow
|
Error
|
Pin assignments
{{@170#bkmrk-pin-assignments}}
C20{{@170#bkmrk--14}}
|
C21
|
C22
|
C23
|
C24
|
C25
|
In the C22 converter user should use only RS232 or only RS485 interface of one port as they occupy the same internal bus of the device.