Data Sheet
HDN1512 HDR1512 HDN2412 HDR3012 HDN5412 HDR6012 HDN9012 HDR10012 HDR10012N
|
Features
- 12 V power supply
- DIN-rail mounting
- UVP (under voltage protection), OCP (over current protection), SCP (short circuit protection) and OVP (over voltage protection)
- 3 years warranty
- Customization of OEM is welcomed
|
Specification
Redisage PN
|
HDN1512 |
HDN2412 |
HDN5412 |
HDN9012 |
Output
|
Rated voltage |
12 V
|
Rated current |
1.25 A |
2 A |
4.5 A |
7.1 A |
Rated power |
15 W |
24 W |
54 W |
90 W |
Adjustment range |
11-13 V |
11.4-12.6 V
|
11-23 V |
Ripple |
150 mVp-p
|
Type |
CV (constant voltage)
|
Efficiency |
83% |
> 85% |
> 86% |
> 89% |
Protection |
OCP, SCP, OVP
|
Input
|
Voltage range |
100-240 VAC
|
Frequency range |
47-53 kHz
|
No load power consumption
|
0.25 W
|
0.35 W |
Protection |
OVP, UVP
|
Temperatures
|
0°C to +40°C
|
Mounting and enclosure
|
DIN rail, 1M |
DIN rail, 2M |
DIN rail, 3M |
DIN rail, 4M |
Redisage PN
|
HDR1512 |
HDR3012 |
HDR6012 |
HDR10012 |
HDR10012N |
Output
|
Rated voltage |
12 V
|
Rated current |
1.25 A |
2 A |
4.5 A |
7.1 A |
7.5 A |
Rated power |
15 W |
24 W |
54 W |
85.3 W |
90 W |
Adjustment range |
10.8-13.8 V
|
12-13.8 V
|
Ripple |
120 mVp-p
|
Type |
CV (constant voltage)
|
Efficiency |
85% |
88%
|
Protection |
OCP, SCP, OVP
|
Input
|
Voltage range |
85-264 VAC / 120-370 VDC
|
Frequency range |
47-53 kHz
|
47-63 kHz
|
No load power consumption
|
< 0.3 W
|
0.35 W |
< 0.3 W |
Protection |
OVP, UVP
|
Temperatures
|
-30°C to +70°C
|
Mounting and enclosure
|
DIN rail, 1M |
DIN rail, 2M |
DIN rail, 3M |
DIN rail, 4M
|
Additional notes
Products family sample photo
https://redisage.com
DISCLAMER NOTES
ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.
Datasheet-ID: (...)