MBus 60-400 Converters & Reapeters Data Sheet
C05 C06 C07 C08 |
Features
|
Introduction
C05 - C08 is a family of products that are reliable M-Bus electrical standard converters. They enable communication in master mode with many (60-400) simultaneously connected slave devices and can work as M-Bus repeaters letting to broaden the range of the interface, while simultaneously making the quality better and supporting the safety of the communication. Dedicated EMC integrated circuits guarantee improved connection quality by limiting the impact of interference typical for an industrial environment.
Specifications
Redisage PN |
C05 |
C06 |
C07 |
C08 |
|
---|---|---|---|---|---|
Converter ports | Serial | 1 x RS232 & 1 x RS485 | |||
M-Bus master | up to 60 slaves | up to 120 slaves | up to 200 slaves | up to 400 slaves | |
M-Bus slave | 1 x M-Bus slave | ||||
Power |
Voltage |
12-30 VDC / 24 VAC |
|||
Max. power | 5 W | 8 W | 15 W | 30 W | |
Frame ground connection | yes | ||||
Serial |
RS232 | TxD, RxD, GND | |||
RS485 | A, B | ||||
3000 VDC isolation side |
RS232, RS485, M-Bus slave |
||||
Baud rate |
up to 9600 bps |
||||
LED indicators | communication Tx, Rx, power, M-Bus load, error | ||||
RS485 termination | 120 ohm manually enabled | ||||
Connector | RS232 | 3 pin terminal block max. 2.5 mm2 wire | |||
RS485 | 3 pin terminal block max. 2.5 mm2 wire | ||||
Power | 3 pin terminal block max. 2.5 mm2 wire | ||||
M-Bus | 3 pin terminal block max. 2.5 mm2 wire | ||||
Transmission |
RS485 |
max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps |
|||
RS232 | max. 15 m at 115.2 kbps | ||||
M-Bus | see: M-Bus max. transmission distance | ||||
Mounting and enclosure | DIN rail, plastic PA - UL 94 V0, black/green | ||||
Temperatures | -40°C to +60°C operating and storage |
||||
Humidity | 10 - 90% RH, non-condensing | ||||
ESD protection |
±4 kV contact discharge / ±8 kV air discharge |
||||
Certification | CE, RoHS |
M-Bus max. transmission distance
Applications
C05 - C08 M-Bus Converter with M-Bus repeater functionality
Frame ground FG
Electronic circuits are constantly prone to electrostatic discharge ESD.
Redisage Electronics modules feature a design for the frame ground terminal block FG.
The frame ground provides a path for bypassing ESD, which provides enhanced static protection ESD abilities and ensures the module is more reliable.
Connecting FG terminal block to the earth ground will bypass the ESD disturbances outside the device so will provide a better level of protection against ESD.
Frame Ground FG connection reference drawing is provided below.
If earth ground is not availabeavailable FG can be left floating or it can be connected with power supply GND.
Pin assignments
C05 |
C06 |
C07 |
C08 |
Enclosure dimensions
2U Module Enclosure.
98 x 56.4 x 35.8
Units: mm.
Additional notes
Related information and links |
||
Ordering information | Accessories | Similar products |
Products family sample photo
DISCLAMER NOTES
ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.