Skip to main content

MBus 60-400 Converters & Reapeters Data Sheet

M-Bus Converters (C05 - C08)

C05 C06 C07 C08

image (6).webp

Features

  • Serial ports RS232 and RS485
  • Up to 400 simultaneously connected slave devices
  • ESD protection for the RS232/485 data line
  • 3000 VDC isolation protection
  • Power supply: +12 to +30 VDC or 24 VAC
  • Transmission speed up to 9600 bps
  • Tx, Rx, power and M-Bus load LED indicators
  • RS485 embedded termination 120 ohm
  • Operating temperatures: -40°C to +60°C
  • DIN-rail mounting
  • Dimensions: 90x56.4x35,6 mm
  • 3 years warranty
  • Customization of OEM is welcomed

Introduction

C05 - C08 is a family of products that are reliable M-Bus electrical standard converters. They enable communication in master mode with many (60-400) simultaneously connected slave devices and can work as M-Bus repeaters letting to broaden the range of the interface, while simultaneously making the quality better and supporting the safety of the communication. Dedicated EMC integrated circuits guarantee improved connection quality by limiting the impact of interference typical for an industrial environment.

Specifications

Redisage PN

C05

C06

C07

C08

Converter ports Serial 1 x RS232 & 1 x RS485
M-Bus master up to 60 slaves up to 120 slaves up to 200 slaves up to 400 slaves
M-Bus slave 1 x M-Bus slave

Power

Voltage

12-30 VDC / 24 VAC

Max. power 5 W 8 W 15 W 30 W
Frame ground connection yes

Serial
interface

RS232 TxD, RxD, GND
RS485 A, B

3000 VDC isolation side

RS232, RS485, M-Bus slave

Baud rate

up to 9600 bps

LED indicators communication Tx, Rx, power, M-Bus load, error
RS485 termination 120 ohm manually enabled
Connector RS232 3 pin terminal block max. 2.5 mm2 wire
RS485 3 pin terminal block max. 2.5 mm2 wire
Power 3 pin terminal block max. 2.5 mm2 wire
M-Bus 3 pin terminal block max. 2.5 mm2 wire

Transmission
Distance

RS485

max. 1,200 m at 9.6 kbps; max. 400 m at 115.2 kbps
(Belden 9841 2P twisted-pair cable, if different cables are used,
the transmission distance may change)

RS232 max. 15 m at 115.2 kbps
M-Bus see: M-Bus max. transmission distance
Mounting and enclosure DIN rail, plastic PA - UL 94 V0, black/green
Temperatures -40°C to +60°C operating and storage
Humidity 10 - 90% RH, non-condensing

ESD protection

±4 kV contact discharge / ±8 kV air discharge

Certification  CE, RoHS

M-Bus max. transmission distance

image.webp

Variants

C05 - C08 M-Bus Converter with M-Bus repeater functionality

Frame ground FG

Electronic circuits are constantly prone to electrostatic discharge ESD. Redisage Electronics modules feature a design for the frame ground terminal block FG. The frame ground provides a path for bypassing ESD, which provides enhanced static protection ESD abilities and ensures the module is more reliable. Connecting FG terminal block to the earth ground will bypass the ESD disturbances outside the device so will provide a better level of protection against ESD.

Frame Ground FG connection reference drawing is provided below.

If earth ground is not available FG can be left floating or it can be connected with the power supply GND.

Pin assignments

C05

image (7).webp

C06

image (8).webp

C07

image (9).webp

C08

image (10).webp

Enclosure dimensions

2U Module Enclosure.

98 x 56.4 x 35.8

Units: mm.

image (11).webp

Additional notes

Products family sample photo

https://redisage.com

DISCLAMER NOTES
ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.

Datasheet-ID: 

SC-D